CYCLONES Range CO, CA,CAN and CD
GENERAL TECHNICAL DATA
Dust collectors of this range are for initially cleaning of air, pulled of local drawing-in facilities, equipment for pneumatic transport, etc. Dust collectors are adapted to functioning as mechanical, inert dust collectors of hard particulates in the suspension in fumes, working with hard oil, with the contaminated air of dryers, dust collectors or from facilities for pneumatic transport with initial level of dust ranging from 0,3 to 400 g/m3.3.
There are not recommended for equipment transferring sticking particles or explosive mixtures.
We offer 4 series of cyclones:
- Series CO
- Series CA
- Series CAN
- Series CD
The series are listed in descending way according to the level of losses of pression and the level of cleaning of the air.
DIMENSIONS
Models and Specifications of the series CO
Type | CA 200 | CA 315 | CA 420 | CA 525 | CA 630 |
Air flow3/h | 400 | 1000 | 1750 | 2700 | 4000 |
Friction loss .Pa | 980 | 1020 | 1080 | 1089 | 1089 |
a | 132 | 205 | 272 | 339 | 408 |
b | 56 | 86 | 113 | 140 | 169 |
fD | 204 | 319 | 424 | 529 | 638 |
fd | 118 | 186 | 248 | 310 | 374 |
fDB | 306 | 478 | 636 | 794 | 957 |
HD | 452 | 712 | 949 | 1186 | 1050 |
HC | 400 | 630 | 840 | 1050 | 1268 |
Hde | 60 | 94 | 126 | 158 | 190 |
HB | 163 | 255 | 339 | 423 | 510 |
H | 912 | 1436 | 1915 | 2394 | 2891 |
HT | 1075 | 1691 | 2254 | 2817 | 3401 |
weightcycloneKg | 7 | 17 | 30 | 47 | 68 |
weightcontainerKg | 5 | 12 | 21 | 33 | 48 |
The shown containers are designed for systems in which the separation of the solid particles has to be done manually and periodically through detachment of the cyclone and emptiness to a special place. Those containers are for single cyclones. We offer specially constructed containers for cyclones batteries.
The shown losses of pressure are for the scheme illustrated on this page - one single cyclone without air facility at the outlet.
The range of dimensions for different series of cyclones is not limited. The company runs a specialized software which generated the design of any kind of cyclone of each of the series adapted to the needs of the client.
Models and Specifications of the series CA
Type | CA 200 | CA 315 | CA 420 | CA 525 | CA 630 |
Air flow3/h | 400 | 1000 | 1750 | 2700 | 4000 |
Friction loss .Pa | 980 | 1020 | 1080 | 1089 | 1089 |
a | 132 | 205 | 272 | 339 | 408 |
b | 56 | 86 | 113 | 140 | 169 |
fD | 204 | 319 | 424 | 529 | 638 |
fd | 118 | 186 | 248 | 310 | 374 |
fDB | 306 | 478 | 636 | 794 | 957 |
HD | 452 | 712 | 949 | 1186 | 1050 |
HC | 400 | 630 | 840 | 1050 | 1268 |
Hde | 60 | 94 | 126 | 158 | 190 |
HB | 163 | 255 | 339 | 423 | 510 |
H | 912 | 1436 | 1915 | 2394 | 2891 |
HT | 1075 | 1691 | 2254 | 2817 | 3401 |
weightcycloneKg | 7 | 17 | 30 | 47 | 68 |
weightcontainerKg | 5 | 12 | 21 | 33 | 48 |
Models and Specifications of the series CAN
Type | CAN 200 | CAN 315 | CAN 420 | CAN 525 | CAN 630 |
Air flow3/h | 400 | 1000 | 1750 | 2700 | 4000 |
Friction loss .Pa | 1020 | 1062 | 1124 | 1134 | 1134 |
a | 132 | 205 | 272 | 339 | 408 |
b | 56 | 86 | 113 | 140 | 169 |
fD | 204 | 319 | 424 | 529 | 638 |
fd | 118 | 186 | 248 | 310 | 374 |
fDB | 306 | 478 | 636 | 794 | 957 |
HD | 302 | 476 | 634 | 793 | 957 |
HC | 300 | 472 | 630 | 787 | 951 |
Hde | 60 | 94 | 126 | 158 | 190 |
HB | 163 | 255 | 339 | 423 | 510 |
H | 662 | 1043 | 1390 | 1783 | 2099 |
HT | 825 | 1298 | 1729 | 2161 | 2609 |
weightcycloneKg | 6 | 15 | 25 | 39 | 56 |
weightcontainerKg | 5 | 12 | 21 | 33 | 48 |
Models and Specifications of the series CD
Type | CD 420 | CD 525 | CD 630 |
Air flow3/h | 2200 | 3500 | 5100 |
Friction loss .Pa | 879 | 887 | 887 |
a | 430 | 536 | 674 |
b | 113 | 140 | 169 |
fD | 424 | 529 | 638 |
fd | 248 | 310 | 374 |
fDB | 636 | 794 | 957 |
HD | 886 | 1108 | 1338 |
HC | 735 | 919 | 1110 |
Hde | 168 | 210 | 254 |
HB | 339 | 423 | 510 |
H | 1789 | 2236 | 2701 |
HT | 2128 | 2659 | 3211 |
weightcycloneKg | 32 | 49 | 71 |
weightcontainerKg | 21 | 33 | 48 |
The shown containers are designed for systems in which the separation of the solid particles has to be done manually and periodically through detachment of the cyclone and emptiness to a special place. Those containers are for single cyclones. We offer specially constructed containers for cyclones batteries.
The shown losses of pressure are for the scheme illustrated on this page - one single cyclone without air facility at the outlet.
The range of dimensions for different series of cyclones is not limited. The company runs a specialized software which generated the design of any kind of cyclone of each of the series adapted to the needs of the client.
TYPE KEY
We indicate the various type-dimensions of cyclones by the following marking: Class and: Nominal diameter.